NAPIT Approved · BS 7671 Section 701 · Part P Notified

Electric Shower Install
8.5kW to 10.8kW
Mid Somerset

Dedicated circuit sized to your shower rating, RCBO at the consumer unit, ceiling-pull or wall-mounted isolator outside zone 2. Like-for-like swaps and new installs. Triton, Mira, Bristan, AKW, Aqualisa supported. From £320 + VAT @ 20%.

07889 334849 · Dan Stevens
Real DS Electrical bathroom install — zone-compliant lighting and shower-circuit ready bathroom in Mid Somerset
NAPIT approved electrical contractorNAPIT
CHAS accredited contractorCHAS
City and Guilds qualified electricianCity & Guilds
TrustMark government endorsedTrustMark
Part P registered electricianPart P
BS 7671 18th Edition compliantBS 7671

Match the circuit to the shower.

An electric shower is the heaviest single circuit in most homes. Get the cable size or breaker rating wrong and the shower trips, the cable overheats, or the unit underperforms. We size each install to the exact unit you specify on the day — and we don’t cut corners on cable.

8.5 kW

Entry-level / second bathrooms

6mm² cable · 32A or 40A RCBO

Common for ensuites and rental properties. Flow is noticeably weaker than a combi shower but adequate for occasional use.

  • Triton T80 series, Mira Sport 8.5kW
  • 32A RCBO if cable run is short
9.5 kW

Most common — family bathroom

6mm² cable · 40A RCBO

The default rating for a single family bathroom. Good balance between flow, running cost and circuit demand.

  • Triton T90sr, Mira Advance 9.8kW
  • Aqualisa Quartz 9.5kW
10.5 kW

Stronger flow — main bathroom

10mm² cable · 50A RCBO

Perceptibly stronger spray. Needs a larger cable and breaker; check your CU has capacity before specifying.

  • Triton Aspirante 10.5kW
  • Mira Advance Flex 10.8kW
10.8 kW

Top-end / accessible installs

10mm² cable · 50A RCBO

Strongest flow available without going to mains-pressure plumbed showers. AKW units common in disabled and assisted-bathing installs.

  • AKW iCare 10.8kW (accessible)
  • Bristan Joy 10.5kW
What’s in every install

The whole job, done properly — not just the unit on the wall.

  • Dedicated circuit from the CU — sized to the kW rating of your shower (6mm² or 10mm²), terminated in an RCBO of the correct rating, never spurred off another circuit.
  • Ceiling-pull or wall isolator outside zone 2 — means the shower can be safely isolated for cleaning, service or replacement without touching the CU.
  • RCBO protection on the new circuit — 30mA personal protection plus dedicated MCB function. Single-circuit RCBO so a fault on the shower doesn’t take out the lighting.
  • Cable run + clean make-good — chase, clip, capping or surface-mount as the property allows. Plaster make-good for chased runs; we don’t leave a trail of scars.
  • Connection at the shower unit — shower terminated to manufacturer instructions, water connection co-ordinated with the plumber if separate.
  • Earthing & bonding check — main equipotential bonding to gas and water verified, supplementary bonding assessed per Reg 701.415.2.
  • Test & certify — insulation resistance, RCD timing, polarity, earth fault loop impedance. Electrical Installation Certificate (or Minor Works for like-for-like swaps).
  • Part P notification via NAPIT — lodged with Building Control on your behalf. You receive both certificates by email within 7 working days.
Real DS Electrical install: zone-compliant bathroom with shower circuit and IP-rated lighting, Mid Somerset

Real DS Electrical install — zone-compliant bathroom with shower-circuit ready board.

Every install, every time.

Whether it’s a like-for-like 9.5kW swap or a brand-new 50A circuit in a house that’s never had an electric shower, the standard is the same. Compliant cable, correct RCBO, isolator outside zone 2, full test pack, Part P notification via NAPIT.

SIZE

Cable sized to unit

6mm² for 8.5/9.5kW, 10mm² for 10.5kW and above. Volt-drop calculated for the actual cable run, not assumed.

RCBO

Dedicated single-circuit RCBO

32A, 40A or 50A as required. RCBO not RCD-on-MCB — a shower fault won’t kill your lights, sockets or boiler.

ISO

Isolator outside zone 2

Ceiling-pull inside the bathroom or wall switch on the hallway side. You choose, we make it compliant.

CU

CU upgrade if needed

Old boards often can’t take a 50A RCBO. We’ll flag it on survey and quote a CU upgrade alongside the shower if needed.

CERT

EIC + Part P notified

Electrical Installation Certificate, or Minor Works for like-for-like. Notification lodged with Building Control via NAPIT.

£

Materials & sundries included

Cable, RCBO, isolator, fixings, chase & make-good, certification, Part P notification — all included in the fixed price.

Pricing ladder.

Final price depends on cable run length, access, existing CU, and whether the unit is supplied by you or by us. Survey is free; written quote is fixed. Read the disclaimer below the cards before assuming.

Like-for-like

Electric shower swap (same kW)

from £320
+ VAT @ 20% · from
  • Existing circuit and isolator retained
  • Customer-supplied unit terminated
  • RCBO checked, test on completion
  • Minor Works Certificate
Heavy

New 10.5kW / 10.8kW install

from £580
+ VAT @ 20% · from
  • New 10mm² circuit + 50A RCBO
  • Cable route survey before quote
  • Suitable for AKW / Mira Advance Flex
  • EIC + Part P notification via NAPIT
Combined

Shower + CU upgrade

from £680
+ VAT @ 20% · from
  • New CU with 18th Ed RCBO bank
  • Dedicated shower circuit added
  • Whole-installation test included
  • EIC + Part P notification via NAPIT
Quote on the day, no obligation. A survey takes about 20 minutes. We check the existing CU, measure the cable run, agree the isolator position, and write you a fixed price — request a survey.
Period bathroom — DS Electrical zone-compliant electric shower install in a Mid Somerset heritage property

From quick swaps to full new installs.

Like-for-like replacement of a tired Triton, a brand-new 50A run from the consumer unit, or a paired CU upgrade and shower install on the same visit — we cover all of it across Wells, Bath, Frome and the surrounding villages.

Common questions.

What kW electric shower do I need?

Higher kW = stronger flow. 8.5kW gives a usable flow but is noticeably weaker than a combi-boiler shower; 9.5kW is the most common all-rounder; 10.5kW or 10.8kW give the strongest flow but need a heavier circuit and a CU that can take a 50A RCBO. We size the circuit to the unit you choose: 8.5kW typically takes 6mm² cable + 32A or 40A RCBO, 9.5kW takes 6mm² + 40A, 10.5kW and above take 10mm² + 50A. Always worth specifying the unit before we quote.

Is electric shower installation notifiable under Part P?

Yes — new circuits in bathrooms (special locations under Part P Schedule 4) are notifiable to your local Building Control. We notify automatically through our NAPIT registration; you do not need to apply separately. Every install ends with an Electrical Installation Certificate plus the NAPIT compliance certificate logged on the national database. Accepted by insurers, mortgage lenders and surveyors.

Where does the pull-cord isolator go?

BS 7671 Section 701 requires the shower isolator to be sited outside zone 1 — in practice that means a ceiling-mounted pull-cord either inside the bathroom outside zone 2, or a wall switch on the hallway side of the bathroom door. Some customers prefer the latter so the cord doesn’t hang in the room. Either is compliant. We agree the position on the survey before we drill anything.

Can my existing fuse board take a new shower circuit?

It depends. Modern dual-RCD or full-RCBO consumer units can almost always accept a new 32A, 40A or 50A RCBO if there’s a free way available. Older boards (Wylex rewireable, Crabtree C50, MEM split-load) often can’t — either no spare ways or no compatible RCBO. In that case the survey will recommend a fuse board upgrade alongside the shower circuit. We’ll always tell you up-front before any work starts.

Do you supply the shower unit or do I buy it?

Either works. Most customers buy the shower unit themselves — Triton, Mira, Bristan, AKW and Aqualisa are all stocked at Screwfix, B&Q and Wickes and you’ll usually pay less direct than we can. Tell us the model when you book and we’ll size the circuit accordingly. If you’d rather we supply, we’ll add it to the quote at trade plus a small handling fee. AKW units are common in accessible-bathroom installs and we’re happy to specify and source those if needed.

Need a new shower circuit? Let’s scope it.

Tell us the kW rating you’re after and we’ll talk you through cable, RCBO, isolator placement and CU capacity. Free survey, fixed quote, NAPIT certified.

07889 334849
Call Dan WhatsApp Free Survey
📞 07889 334849
Call Dan07889 334849 WhatsAppQuick reply Emailinfo@